• <b id="h1pkn"><address id="h1pkn"></address></b>
  • <source id="h1pkn"></source>

  • <tt id="h1pkn"><source id="h1pkn"></source></tt>
    <xmp id="h1pkn"></xmp>
    <b id="h1pkn"></b>

    <source id="h1pkn"><address id="h1pkn"><kbd id="h1pkn"></kbd></address></source>
    <u id="h1pkn"><small id="h1pkn"></small></u>
    <b id="h1pkn"></b>
      <b id="h1pkn"></b>
      <xmp id="h1pkn"></xmp>
    1. Welcome to"Suzhou Doer Gas & Chemical Equipment Co., Ltd" website!

      Hotline: +86 512-81666096
      0512-66182570

      Hotline

      +86 512-81666096
      Forum

      Now:Home > News > Forum

      123,20000m 3 Dry powder calculation of LNG full capacity tank (Part 2) - Doer equipment

      Classification:Forum PublishTime:2019-11-20 13:59:04

      20000m 3 Dry powder calculation of LNG full capacity tank (Part 2)


      20000m 3 Dry powder calculation of LNG full capacity tank (Part 2)


      The system design adopts the local application fire extinguishing method, and the volume method is used for calculation. Assume that the peripheral shape is a box:


      Length: 0.355 + 1.5 × 1.5=2.605m


      Width: 0.355 + 1.5 × 1.5=2.605m


      Height: 1.5 + 1.5 × 1=3 m


      The calculated volume of the protected object is 3v1 = 3 × two point six zero five × two point six zero five × 3=61.07m 3


      Injection rate: QV = 0.04-0.006 ×( three point one four × zero point three five five × 1.5)/ (2.605 × two point six zero five × 3)


      =0.0395


      m= 3 × V1 × qv × t=61.07 × zero point zero three nine five × 60=144.7Kg


      Dry powder calculation


      The total spray strength of dry powder is (61.07 × 0.0395) = 2.41kg/s, 4 local application nozzles are designed for each vent, and the injection intensity of each nozzle is (2.41 / 4 / 2) = 0.301kg/s. According to the type selection report of the dry powder manufacturer, the nozzle with spraying intensity of 0.68 kg / S (0.68 > 0.301) is selected. If the spraying time is 60s, the total spraying amount is 0.68 × four × 60 = 163.2kg, plus 10% margin, and the required dry powder amount is 163.2 × 1.1 = 179.52kg, so zfp250 dry powder fire extinguishing system is selected and filled with 250kg dry powder, which can fully meet the requirements. In this project, zfp500 dry powder fire extinguishing system is selected and filled with 500kg dry powder, which can fully meet the requirements.




      Home Product Case Top
    2. <b id="h1pkn"><address id="h1pkn"></address></b>
    3. <source id="h1pkn"></source>

    4. <tt id="h1pkn"><source id="h1pkn"></source></tt>
      <xmp id="h1pkn"></xmp>
      <b id="h1pkn"></b>

      <source id="h1pkn"><address id="h1pkn"><kbd id="h1pkn"></kbd></address></source>
      <u id="h1pkn"><small id="h1pkn"></small></u>
      <b id="h1pkn"></b>
        <b id="h1pkn"></b>
        <xmp id="h1pkn"></xmp>
      1. 幻女bbwxxxx4444